Phone
WhatsApp
Email

SWITCHGEAR

Armored removable AC metal enclosed switchgear

Description of High Voltage Switchgear KYN61-40.5(Z) type alternating current metal-clad and metal-enclosed with drawable switchgear (hereinafter referred to as switchgear) is a indoor complete set of power distribution unit of three- phase

contact info

product description

Description of High Voltage Switchgear

KYN61-40.5(Z) type alternating current metal-clad and metal-enclosed with drawable switchgear (hereinafter referred to as switchgear) is a indoor complete set of power distribution unit of three- phase AC 50HZ and rated voltage of 40.5 kV.Uses for receiving and distributing the electric energy in power plants, transformer substations,mining and industrial enterprises,ect.,it controls, protects and detects the circuits, also is applicable to frequent operation locatons. This switchgear complies with GR/T11022-1999,GB3906-1991,DL404-1997,ect.

Use environmental conditions of High Voltage Switchgear

1. Environment temperature: -10 ℃ ~+40℃,averagevalue measured within 24h should not cxceed 35℃.

2. Altitude: ≤1000m;

3. Relative humidity: daily ≤95%. monthly ≤90%;

4. Seismic intensity:≤s8;

5. Vapor pressure: daily≤2.2kPa, monthly ≤1.8kPa.

6. Ambient environment: the installation site should be free of fire, explosive danger, serious pollution, chemical corrosion or severe vibration.

Main feature of High Voltage Switchgear

1. Cabinet structure is of assembled type,the circuit breaker adopts floor type handcart structure;

2. Equipped with brand new composite insulated vacuum circuit breaker, is featured with good interchangeability, and is simple to change;

3. The hand cart frame is mounted with lead screw nut propelling mechanism, it is able to move the handcart easily, and prevent damage of propelling mechanism caused by misoperation;

4. All operations can be carried out when the cabinet door is closed;

5. Interlocking among the main switch, handcart and switchgear adopts compulsory mechanical locking mode, meeting the "five preventions" function;

6. Cable chamber is large enough, it could connect multi cables;

7. The fast earthing switch is used for earthing and circuit short-circuit

8. The protection of the enclosure is IP3X, and is IP2X when the door of handcart chamber is opened;

The product complies with GB3906-199L,DL404-1997 and refers to IEC-298.Vacuum breaker switchgear main technical parameter

Name Unit Value
Rate voltage KV 40.5
Rate current A 1250  1600 2000
Rated frequency HZ 50

Rated short-time withstand current

KA

20 25 31.5

Rated peak withstand current

KA

50 63 80

Rated power frequency withstand voltage

KV

95/1min

Rated lighting impulse withstand voltage

KV

185

Rated short-circuit duration

S 4

Degree of protection

 

IP3X

 

leave a message

If you are interested in our products, please feel free to contact us!or send email to us!Email address:sales@ztelecgroup.com

more+fetured products
email whatsapp inquiry